FREQUENTLY ASKED QUESTIONS

35 Diesel Fire Pump Installation

Fire Pump Systems

Alarm on control panel

  • Which LED is lit? Check fault in manual
  • Press stop/restart button
  • Is the fire hydrant open? The bell will ring when pump is running (close hydrant and press stop/reset)

Cooling loop hose disconnected from engine

  • Did engine run? If so, check it has not seized – Engine may need to be replaced
  • Is PRV on cooling adjusted correctly?
  • Reattach hose securely and retest system

What size plinths?

5Hid20112597 – Single Diesel System

Pumpset baseplates shall be mounted on concrete plinths with a height not less than 150mm above the floor.

For fixing purposes, the concrete plinth shall extend 150 mm past the edge of the baseplate on all four sides.

Current-carrying parts of motors and fire pump controllers shall be not less than 300 mm from the floor.